§ 8B-2. Amendments, additions, and deletions to the 2015 edition of the International Building Code.  


Latest version.
  • (a)

    Amendments included in this section are intended to be specific code provisions. If there is a conflict between a provision in the published 2015 International Building Code and this section, the specific provisions of this section shall control.

    (b)

    The following table contains the local amendments to the International Building Code, which is modified as set forth herein:

    (1)

    When identified by the letter "R," the corresponding section of the 2015 International Building Code is deleted in its entirety and replaced by the local amendment as set forth in Column 3 of the table below.

    (2)

    When identified by the letter "S," the corresponding section of the 2015 International Building Code is supplemented by the additional provision as set forth in Column 3 of the table below.

    (3)

    When identified by the letter "M," the corresponding section of the 2015 International Building Code is modified by amending the language of the provision to read as set forth in Column 3 of the table below.

    Table Legend:

    Column 1: Item Reference Number

    Column 2: Related code section/caption

    Column 3: Amended code provision

    Column 4: "R" - 2015 International Building Code section is replaced by the provision in Column 3; "S" - 2015 International Building Code section is supplemented by the provision in Column 3; "M" - 2015 International Building Code section is modified by the provision in Column 3.

    TABLE OF LOCAL AMENDMENTS TO THE 2015 INTERNATIONAL BUILDING CODE

    1 IBC 101.4
    Referenced codes and
    standards
    Codes when specifically adopted, and standards referenced in the codes shall be considered part of the requirements of the code to the prescribed extent of each such reference and as further regulated on the codes. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well.
     a. Any reference made to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted.
     b. The provisions of the Electrical Code shall apply to both residential and commercial installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto.
    R
    2 IBC 103.1
    Department of building safety
    Wherever the term "department of building safety" is used, it shall mean the department of inspections.
    M
    3 IBC 104.2
    Applications and permits
    Construction in flood hazard areas shall be in conformance with Chapter 47 "Flood Damage Prevention" of The Irving Land Development Code of the City of Irving, Texas.
    R
    4 IBC 104.10.1
    Flood hazard
    areas
    Construction in flood hazard areas shall be in conformance with Chapter 47 "Flood Damage Prevention" of The Irving Land Development Code of the City of Irving, Texas.
    R
    5 IBC 105
    Permits
    a. Dormant permit applications . Permits that have been approved for which payment has not been received within 14 days may be cancelled.
    b. Lack of progress . Permits may be cancelled for a lack of reasonable progress comparable to similar projects.
    c. Accessory buildings . A permit issued for the construction of an accessory building shall be valid for a period of 3 months from the date of issuance. The building official shall be authorized to extend this initial 3-month period for one additional 3-month period after a determination that the property complies with all city ordinances.
    S
    6 IBC 105.2
    Work exempt from permit
    a. One-story detached accessory structures used as tool and storage sheds, playhouses, and similar uses, not exceeding 6 feet in any dimension (includes height measured from adjacent grade to the highest point of the roof).
    b. Fences require permits in accordance with Chapter 15 "Fences" of The Land Development Code of the City of Irving, Texas.
    c. Installation or repair of retaining walls which are not over 30 inches in height of exposed face, unless supporting a surcharge or impounding Class I, II, or III-A liquids.
    d. Sidewalks not exceeding 4 feet in width, which are:
     1) On private property;
     2) Not more than 30 inches above adjacent grade; and
     3) Not over any basement or story below.
    e. Paving or driveways, which are:
     1) On private property;
     2) Not exceeding 1,000 square feet in area;
     3) Not creating or reconfiguring parking spaces; and
     4) Not replacing any required landscape area.
    f. Swings and other playground equipment other than indoor children's play structures as regulated by this code.
    M
    7 IBC 109
    Fees
    Refer to Section 8B-3 of Chapter 8B of The Land Development Code of the City of Irving, Texas. S
    8 IBC 111
    Certificate of occupancy
    a. Certificate of use . No lot or tract of property upon which there has been no building or structure constructed shall be used or occupied, and no change in the existing use of the property or portion thereof shall be made until the building official has issued a certificate of use.
    b. Letter of compliance . The building official shall issue a letter of compliance for buildings which have received shell construction final inspections from both the inspections and fire departments.
    S
    9 IBC 111.2
    Certificate issued
    The name of the tenant is required to be provided on certificate of occupancy applications.
    S
    10 IBC 113
    Board of appeals
    Refer to Section 8B-4 of Chapter 8B of The Land Development Code of the City of Irving, Texas.
    R
    11 IBC 202
    Definitions
    a. Ambulatory health care facility . Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing, or similar care on a less than 24-hour basis to individuals who are rendered incapable of self-preservation. This group may include, but not be limited to, the following: dialysis centers, sedation dentistry, surgery centers, colonic centers, or psychiatric centers.
    b. Atrium . An opening connecting three or more stories other than enclosed stairways, elevators, hoist ways, escalators, plumbing, electrical, air-conditioning, or other equipment, which is closed at the top and not defined as a mall. Stories, as used in this definition, do not include balconies within assembly groups or mezzanines that comply with Section 505.
    M
    12 IBC 202
    Definitions
    a. Building official . The city manager's designee to this position or his or her designated representative.
    b. Fire chief . The chief of the City of Irving Fire Department or a duly authorized representative.
    S
    13 IBC 304.1
    Business group B
    Business Group B occupancies include fire stations and police stations with detention facilities for 5 or less.
    S
    14 IBC 403.3
    Automatic sprinkler system
    Automatic fire sprinkler systems are required in high-rise telecommunication equipment buildings.
    M
    15 IBC 406.3.5.1
    Carport
    separation
    A separation is not required between a Group R-2 and U carport, provided that the carport is non-combustible and entirely open on all sides and that the distance between the two is at least 10 feet.
    S
    16 IBC 406.8
    Repair garages
    Repair garages shall include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement, and other such minor repairs.
    S
    17 IBC 506.3
    Frontage increase
    If not in direct contact with a street or fire lane, a minimum 10-foot wide pathway meeting fire department access from the street or approved fire lane shall be provided, in order to be considered as accessible.
    S
    18 IBC 716.5.9.4
    Doors in pedestrian ways
    Vertical sliding or vertical rolling fire doors are prohibited in openings through which pedestrians, fire fighters, or emergency responders travel.
    R
    19 IBC 1009.1
    Accessibility means of egress
    Buildings regulated under state law and built in accordance with state registered plans, including any variances or waivers granted by the state, shall be deemed to be in compliance with the accessible means of egress requirements of the code.
    S
    20 IBC 1010.1.9.4
    Bolt locks
    Where a pair of doors serves an occupant load of less than 50 persons in a Group M occupancy, manually operated edge or surface mounted bolts are allowed on the inactive leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware.
    S
    21 IBC 1017.2.2
    Group F-1 and S-1 increase
    The maximum exit access travel distance shall be 400 feet in Group F-1 or S-1 occupancies where all of the following conditions are met:
    a. The portion of the building classified as Group F-1 or S-1 is limited to one story in height;
    b. The minimum roof height from the finished floor to the bottom of the ceiling or roof deck is 24 feet;
    c. The building is equipped with an automatic sprinkler system; and
    d. The building is equipped with manual heat and smoke roof vents in accordance with the code
    S
    22 IBC 1101
    Texas Accessibility Standards
    Compliance . Buildings regulated under state law and built in accordance with state registered plans, including any variances or waivers granted by the state, shall be deemed to be in compliance with the accessibility requirements of this code.
    S
    23 IBC 1106.5
    Van spaces
    For every four or fraction of four accessible parking spaces, at least one shall be a van-accessible parking space. If two or more accessible parking spaces are provided, the first two accessible parking spaces shall be van-accessible.
     Exception: In Group R-2 and R-3 occupancies, van-accessible spaces located within private garages shall be permitted to have vehicular routes, entrances, parking spaces and access aisles with a minimum vertical clearance of 7 feet.
    R
    24 IBC 1111.1 #1
    Signage
    All accessible parking spaces shall be identified with signs which contain the International Symbol of Accessibility.
    R
    25 IBC 1207
    Sound
    Transmission
    a. Two zones . For the purposes of this code, certain sections of the city are zones subject to significant noise from aircraft. These zones are the "65-70 DNL noise zone" and the "over 70 DNL noise zone."
    b. Map . These noise zones shall include such territory or portions of the city as are designated and shown on the aircraft noise impact map (a copy of which is on file with the building official) and incorporated into this code and made a part of it for all intents and purposes.
    c. Certified plans . The building official shall not issue a building permit for any building or structure within the noise zones shown on the aircraft noise impact map unless the plans and specifications accompanying the application for the permit are certified by a bona fide acoustical consultant as meeting the required noise level reduction standards of this section.
    d. Noise consultants . Bona fide acoustical noise consultants include members of the National Council of Acoustical Consultants and others who are approved by the building official, such approval being based on the demonstration of competence and credentials in the area of architectural acoustics.
    e. Building intrusion in a noise zone . A building or structure which is located partly within a noise zone and partly without or located partly within one noise zone and partly within another noise zone shall be considered within the most restrictive of the noise zones within which it is located for purposes of this section.
    f. Noise reductions standards . Plans for the construction of buildings or structures within noise zones shall be certified as achieving at least the outdoor to indoor noise level reductions as measured in decibels within the building as follows:
    S
    Building Use 65-70 DNL
    Noise Zone
    Over 70 DNL
    Noise Zone
    Residential:
    Residential within each unit including transient lodgings.
    25 30
    Public Use:
    Schools, hospitals, and nursing homes
    25 30
    26 IBC 1505
    Fire classification
    Non-classified roof coverings shall be permitted on buildings of Group U occupancies having not more than 120 square feet of projected roof area. When exceeding 120 square feet of projected roof area, buildings of Group U occupancies may use non-rated non-combustible roof coverings.
    S
    27 IBC 1511
    Reroofing
    a. All individual replacement shingles or shakes shall be in compliance with the minimum rating required by this code.
    b. No more than two layers of asphalt shingles shall be installed.
    c. New roof coverings shall not be installed on an existing roof deck that does not comply with the requirements of this code for new construction. An additional layer of code compliant decking may be installed over an existing roof deck in lieu of its removal.
    S
    28 IBC 1705.17
    Fire-resistant penetrations and joints
    Fire-resistant rated penetrations and joints . In high-rise buildings; buildings assigned to a Risk Category III or IV; and in R-1 and R-2 portions of buildings, special inspections shall be provided for through penetration and membrane penetration firestops; fire-resistant joint systems; and perimeter fire barrier systems.
     Exception: R-1 or R-2 occupancies not located in high-rise buildings if the installation of the products or systems is performed by an installer approved by both the product manufacturer and the building official.
    R
    29 IBC 1807.2
    Retaining Walls
    a. Retaining walls shall be designed, inspected, and approved by a registered structural engineer.
    b. Retaining walls which require a permit shall not be constructed of wood.
    c. Property restrictions. The proper performance of retaining walls shall not be based on restrictions or requirements placed on property owners which will require future design or review by the retaining wall design engineer. Any exposed soil in the vicinity of a retaining wall shall be assumed to be landscaped and irrigated. Restrictions which may deprive property owners from full use and enjoyment of property shall not be included in the design or related maintenance requirements of a retaining wall.
      Exception: Restrictions clearly stated in easements which are designated on the subdivision plat of record.
    S
    30 IBC 2103.1
    Masonry units
    Clay brick used outdoors shall meet Grade SW (severe weather) requirements of either ASTM C 216 or ASTM C 652.
    S
    31 IBC 2902.1
    Minimum number of fixtures
    Plumbing fixtures shall be provided for the type of occupancy and substantially in compliance with the minimum number as specified by the codes.
    M
    32 IBC 3002.1
    Hoistway enclosure protection
    Elevator hoistways are not required to be constructed as shafts when they are located entirely with atriums, open parking garages or enclosed parking garages.
    S
    33 IBC 3005
    Machine rooms
    a. Storage shall not be allowed within the elevator machine room.
    b. Approved durable signage on a contrasting background shall be provided at each entry door to the elevator machine room stating "Elevator Machinery - No Storage Allowed."
    S
    34 IBC 3301.2
    Storage and placement
    a. Equipment and material storage . Construction equipment and materials may be stored on-site if:
     1) They are being used in a construction project for which a valid permit is in effect and for which reasonable progress is being made; or
     2) They are associated with work of a nature for which no permit is required, and they are stored on-site for only one period of time no longer than ten consecutive days within any six month period; or
     3) A construction scope and schedule is approved by the department of inspections to allow storage of materials associated with:
      i. Work for which a permit is required, but reasonable progress is not being made; or
      ii. Work for which a permit is not required and a time period of more than ten days is needed to complete the work.
    S
    35 IBC 3302
    Construction safeguards
    a. Waste materials . Litter and light-weight construction waste materials such as food wrappers and construction material packaging shall be placed in a container that prohibits the waste materials from blowing onto adjacent properties. Waste material containers shall be maintained in an approved location and shall be removed in a manner which prevents injury or damage to persons, adjoining properties, and public rights-of-way.
    b. Mowing . Job-site properties shall be kept mowed and trimmed in accordance with Chapter 33 of The Code of Civil and Criminal Ordinances of the City of Irving, Texas.
    S
    36 IBC 3303
    Demolitions
    a. Demolition resulting in a vacant lot. All portions of structures, appurtenances, paving, flatwork, pool decks, incidental accessory structures, and construction debris shall be removed from the site. The site shall be graded to allow for proper drainage and for the property to be mowed.
     Exception: Partial demolition and reuse of the principal structure in accordance with an approved permit.
    b. Utility connections . Franchise utility connections shall be discontinued and removed in accordance with the approved rules and the requirements of the applicable franchise utility. Overhead service drop lines shall be removed from utility poles. Water and sewer lines shall be removed and capped in accordance with the policy established by the director of water utilities or his designee.
    S
    37 IBC 3304.1
    Excavation and fill
    Neither construction debris, organic materials, nor trash shall be buried in utility ditches or other on-site excavations. S
    38 IBC 3305.1
    Facilities required
    Temporary toilet facilities shall be fully enclosed, chemically sanitized, and serviced and cleaned at least once each week.
    S
    39 Chapter 34
    Existing Buildings
    a. Buildings in existence at the time of adoption of the code may have their existing use or occupancy continued, if such use or occupancy was legal at the time of the adoption of the code, provided such use is not dangerous to life.
    b. Maintenance . All buildings and structures, both existing and new, and all parts thereof, shall be maintained in a safe and sanitary condition. All devices or safeguards required by this code shall be maintained in conformance with the code edition under which installed. The owner or owner's design agent shall be responsible for the maintenance of buildings and structures. To determine compliance with this subsection, the building official may cause a structure to be reinspected.
    c. Additions, alterations, or repairs .
     1) General . Additions, alterations, or repairs may be made to any building or structure without requiring the existing building or structure to comply with all the requirements of the code, provided the addition, alteration, or repair conforms to that required for a new building or structure.
     2) Unsafe conditions . Additions or alterations shall not be made to an existing building or structure that will cause the existing building or structure to be in violation of any of the provisions of the code and such additions or alterations shall not cause the existing building or structure to become unsafe. An unsafe condition shall be deemed to have been created if an addition or alteration will:
      i. Cause the existing building or structure to become structurally unsafe or overloaded,
      ii. Not provide adequate egress in compliance with the provisions of the code,
      iii. Obstruct exists,
      iv. Create a fire hazard,
      v. Reduce required fire resistance
      vi. Otherwise create conditions dangerous to human life.
     3) Area and height . Any building plus new additions shall not exceed the height, number of stories and area specified for a new building.

     


     4) Non-conforming buildings or structures . Additions or alterations shall not be made when such existing building or structure is not in full compliance with the provisions of the code except when such addition or alteration will result in the existing building or structure being no more hazardous related to life safety, fire safety, or sanitation than before such additions or alterations are undertaken.
     5) Nonstructural . Alterations or repairs to an existing building or structure that are nonstructural and do not adversely affect any structural member or any part of the building or structure having required fire resistance may be made with the same materials of which the building or structure is constructed.
     6) Glass replacement . The installation or replacement of glass shall be as required for new installations.
     7) Historic buildings . Repairs, alterations, and additions necessary for the preservation, restoration, rehabilitation, or continued use of a building or structure may be made without conformance to all the requirements of the code when authorized by the building official, provided:
      i. The building or structure has been designated by official action of the legally constituted authority of this jurisdiction as having special historical or architectural significance.
      ii. Any unsafe conditions as described in the code are corrected.
      iii. The restored building or structure will be no more hazardous related to life safety, fire safety, or sanitation than the existing building.
     8) Moved buildings . Buildings or structures moved into or within the jurisdiction shall comply with the provisions of the code for new buildings or structures.

     


     9) Change in use . No change shall be made in the character of occupancies or use of any building that would place the building in a different division of the same group of occupancy or in a different group of occupancies, unless such building is made to comply with the requirements of the code for such division or group of occupancy.
      Exception: The character of the occupancy of existing buildings may be changed subject to the approval of the building official, and the building may be occupied for purposes in other groups without conforming to all the requirements of the code for those groups, provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use.

     

(Ord. No. 2015-9746, § 2, 12-10-15)